Overvoltage protection for msr signals




Дата канвертавання22.04.2016
Памер18.54 Kb.

I

page / I


Tender text "Overvoltage protection for MSR signals "


MCZovp with three-stage overvoltage protection

Overvoltage protection in slim terminal housing (6mm) with PE contact and spring clamp connection in sizes 0.5 to 1.5mm². The PE connection is made by snapping onto an earthed 35mm mounting rail . The signal to PE using is protected using gas discharge tubes and varistors and between the lines using high-speed suppression diodes.


Applications include current loops 0(4) to 20mA and 0 to 10 V signals

Technical data

Rated voltage: 24V

Resistance per path: 2.5 ohms at 0.5A or 1 ohms at 1.25A

Protection level on output side, symmetric

For 1 kV/µs pulse at input, typical: 40V


Ordering data:

Make: Weidmüller

Type : MCZ OVP CL 24Vdc 0.5A

Order No. 8448920000


Ordering data:

Make: Weidmüller

Type : MCZ OVP CL 24Vac 0.5A

Order No. 8472880000


Ordering data:

Make: Weidmüller

Type : MCZ OVP CL 24Vac 1.25A

Order No. 8448960000


Application: binary signals (24V switching signals)
Ordering data:

Suitable for 2 switching signals

Make: Weidmüller

Type : MCZ OVP SL 24Vdc 0.5A

Order No. 8448940000
Ordering data:

Suitable for 2 switching signals

Make: Weidmüller

Type : MCZ OVP SL 24Vac 1.25A

Order No. 8448970000

Application: binary signals (48V switching signals)
Ordering data:

Suitable for 2 switching signals

Make: Weidmüller

Type : MCZ OVP SL 48Vdc 0.5A

Order No. 8449030000
Ordering data:

Suitable for 2 switching signals

Make: Weidmüller

Type : MCZ OVP SL 48Vac 1.25A

Order No. 8449050000

Application: binary signals (115V switching signals)
Ordering data:

Suitable for 2 switching signals

Make: Weidmüller

Type : MCZ OVP SL 115Vac 1.25A

Order No. 8449070000
Application: binary signals (230V switching signals)
Ordering data:

Suitable for 2 switching signals

Make: Weidmüller

Type : MCZ OVP SL 230Vac 1.25A

Order No. 8449090000

MCZovp with individual components

Overvoltage protection in slim terminal housing (6mm) with PE contact and spring clamp connection in sizes 0.5 to 1.5mm². The PE connection is made by snapping onto an earthed 35mm mounting rail . Two signals are protected using individual components such as gas discharge tubes, varistors or suppression diodes.


Application: protective circuits using varistors

Technical data

Rated voltage: 24V

Resistance per path: 0.2 ohms

Protection level on output side, symmetric

For 1 kV/µs pulse at input, typical: 45V

Suitable for 2 signals
Ordering data:

Make: Weidmüller

Type : MCZ OVP varistors S10k30

Order No. 8449140000



Application: protective circuits using varistors

Technical data

Rated voltage: 60V

Resistance per path: 0.2 ohms

Protection level on output side, symmetric

For 1 kV/µs pulse at input, typical: 700V

Suitable for 2 signals
Ordering data:

Make: Weidmüller

Type : MCZ OVP gas discharge tube 90V

Order No. 8449130000


Application: protective circuits using suppression diodes

Technical data

Rated voltage: 24V

Resistance per path: 0.2 ohms

Protection level on output side, symmetric

For 1 kV/µs pulse at input, typical: 55V

Suitable for 2 signals
Ordering data:

Make: Weidmüller

Type : MCZ OVP TAZ diodes 24Vdc

Order No. 8449150000



Application: protective circuits using suppression diodes

Technical data

Rated voltage: 24Vac

Resistance per path: 0.2 ohms

Protection level on output side, symmetric

For 1 kV/µs pulse at input, typical: 55V

Suitable for 2 signals
Ordering data:

Make: Weidmüller



Type : MCZ OVP TAZ diodes 24Vac

Order No. 8449160000